The HAES ESEN-8MAR Esento Marine provides 8 conventional fire detection zones. All inputs and outputs are fully programmable and there are options to have delays to the outputs. The programming features also include a muster alarm feature and 3 different modes to help reduce false alarms.
As standard, all Esento Marine 8-12 panels provide four monitored sounder circuits, Fire & Fault VFCO relays, Fire & Fault switched negative outputs and inputs to ring and pulse the sounder circuits.
A fully functional repeater panel is available via a plug in comms PCB.
A separate interface card is also available to connect the panel to a ships voyage data recorder system.
The panels are supplied with a 3.0 amp internal power supply module. This module complies with the requirements of EN54-4 : 1988 and provides temperature-compensated battery management charging.
Esento Marine panels are approved to European standards EN54-2 & 4, Fire Detection and Alarm Systems – Control & Indicating Equipment
Key Features of the ESEN-8MAR |
|---|
| > 8 conventional zones > Network up to 8 control panels > Activate controls via key switch or code entry > Compatible with Apollo Orbis Marine detectors > Integral detector removal monitoring > Earth fault monitoring > 3 Amp switch mode power supply Nom 27V DC > 4 monitored sounder outputs > 2 Aux C/O relays (1 x Fire) (1 x Fault). voltage free > Class change I/P > Alert I/P > Fire & fault switched -ve outputs > Program delays to outputs > False alarm modes A, B & C > Muster alarm > Test mode, with or without sounders > Disable zones, sounder O/Ps, aux O/Ps & delays > Alarm load, 2.4A shared between all sounder outputs > All sounder circuits are fused @ 500mA with resettable fuses |
| Brand | HAES Technologies |
|---|---|
| Manufacturer Part No. | ESEN-8MAR |
| Product Series | Esento Marine |
| Primary Power Source | Mains Powered (230V) |
| System Type | Conventional |
| Number of Zones | 8 |
| Colour | Grey |
| Warranty | 3 Years |
| Enclosure | 1.2mm Mild Steel IP30. Colour ref: MW334E Interpon powder coat |
| Cable Entry | Via 20mm knockouts located in the top and rear of the cabinet |
| Dimensions | Back box: 450mm W x 300mm H x 85mm D, Lid: 460mm W x 310mm H x 25mm D |
| Mains Supply | 3A internal switch mode power supply, Nom 27v DC |
| Battery Capacity | 2 x 7.0Ah 12v VRSLA |
| Detection Zones | 8 x conventional. EOL = 4K7R |
| Sounder Circuits | 4 x monitored, fused @500mA. EOL = 4K7R |
| Networking | Up to 8 control panels, fault-tolerant RS485 communication, requires TPCA05 network card |
| On Board Relays | 2 x programmable, 3A, 30v volt free changeover, additional relay provided on high spec zone card |
| Outputs | 2 x programmable, 40mA switch -ve, 2 additional outputs provided on high spec zone card |
| Switch Inputs | Class change & alert (pulsing) |
| Event Log | 40 event history |
| Intrinsically Safe Mode | Selectable per zone |
| False Alarm Management | Type A, B & C dependency modes, approved by LPCB |
| Delay Timer | On board programmable delay timer 1-10 mins |
| Muster Alarm | Selectable per zone |