The HAES ALS-2 AlarmSense is a 2 zone Apollo Fire Detectors AlarmSense protocol two-wire conventional control panel with integral power supply & space for standby batteries.
Two AlarmSense fire zone circuits are provided plus two additional conventional monitored sounder circuits. Fire & Fault VFCO relays, Fire & Fault switched negative outputs, class change and an alert input are also included. AlarmSense panels support the full range of Apollo Fire Detectors AlarmSense devices.
The panels are supplied with a 1.25 amp internal power supply module. This module complies with the requirements of EN54-4 : 1988 and provides temperature compensated battery management charging.
HAES AlarmSense panels are fully approved to European standards EN54-2 & 4, Fire Detection and Alarm Systems – Control & Indicating Equipment.
Key Features of the ALS-2 |
|---|
| > 2 x AlarmSense zones > Compatible with Apollo AlarmSense range of devices > Activate controls via key switch or code entry > Integral detector removal monitoring > 1.25 Amp switch mode power supply Nom 27V DC > 2 x conventional monitored sounder outputs > 2 Aux C/O relays (1 x Fire) (1 x Fault). voltage free > Class change I/P > Alert I/P > Fire & fault switched -ve outputs > Test mode, with or without sounders > Disable zones, sounder O/Ps & aux O/Ps > Conventional sounder circuits are fused @ 500mA with resettable fuses |
| Brand | HAES Technologies |
|---|---|
| Manufacturer Part No. | ALS-2 |
| Product Series | HAES AlarmSense |
| Primary Power Source | Mains Powered (230V) |
| System Type | 2-Wire |
| Number of Zones | 2 |
| Colour | Grey |
| Warranty | 3 Years |
| Enclosure | 1.2mm Mild Steel IP30. Colour ref: MW334E Interpon powder coat |
| Cable Entry | Via 20mm knockouts located in the top and rear of the cabinet |
| Dimensions | Back box: 300mm W x 250mm H x 80mm D, Lid: 308mm W x 260mm H x 23mm D |
| Mains Supply | 1.25A internal switch mode power supply, Nom 27v DC |
| Battery Capacity | 2 x 3.2Ah 12v VRSLA |
| Detection Zones | 2 x AlarmSense protocol. EOL = 3K3R |
| Sounder Circuits | 2 x conventional monitored, fused @500mA. EOL = 3K3R |
| On Board Relays | 1 x Fire, 1 x Fault, 3A, 30v volt free changeover |
| Outputs | 1 x Fire, 1 x Fault 40mA switch -ve outputs |
| Switch Inputs | Class change & alert (pulsing) |
| Non Priority Alarm | Selectable per zone |
| Coincidence Alarm | Selectable per zone |